JOURNAL OF YANGTZE RIVER SCIENTIFIC RESEARCH INSTI ›› 2016, Vol. 33 ›› Issue (2): 128-130.DOI: 10.11988/ckyyb.20140834

• INSTRUMENTATION DEVELOPMENT AND TESTING TECHNIQUE • Previous Articles     Next Articles

Application of Constant α Control Method of Excitation Regulator in Shenwo Power Plant

TIAN Bo, YANG Fa-hong   

  1. Shenwo Reservoir Administration Bureau of Liaoning Province, Liaoyang 111000,China
  • Received:2014-09-28 Published:2016-02-01 Online:2016-02-17

Abstract: In this paper, we introduce the control mode of excitation regulator with constant α. WL-06B double-microcomputer excitation regulator in Shenwo power plant of Liaoning province is taken as an example. By changing the induction generator from self-shunted type into separately-excited type, we carry out three-phase short-circuit test for steady-state characteristics of generator, and obtain characteristic curve of the test. Moreover, we obtain the three-phase current of stator winding by altering the control angle and excitation current of rotor winding. We can also determine the symmetry of three-phase current and identify short-circuit failures among windings of rotor by using the characteristic curve. The research results offer reference for similar tests in the future.

Key words: excitation regulator, control mode of constant α, stator winding, short-circuit test, Shenwo power plant

CLC Number: