Journal of Changjiang River Scientific Research Institute ›› 2016, Vol. 33 ›› Issue (2): 128-130.DOI: 10.11988/ckyyb.20140834
• INSTRUMENTATION DEVELOPMENT AND TESTING TECHNIQUE • Previous Articles Next Articles
TIAN Bo, YANG Fa-hong
Received:
Published:
Online:
Abstract: In this paper, we introduce the control mode of excitation regulator with constant α. WL-06B double-microcomputer excitation regulator in Shenwo power plant of Liaoning province is taken as an example. By changing the induction generator from self-shunted type into separately-excited type, we carry out three-phase short-circuit test for steady-state characteristics of generator, and obtain characteristic curve of the test. Moreover, we obtain the three-phase current of stator winding by altering the control angle and excitation current of rotor winding. We can also determine the symmetry of three-phase current and identify short-circuit failures among windings of rotor by using the characteristic curve. The research results offer reference for similar tests in the future.
Key words: excitation regulator, control mode of constant α, stator winding, short-circuit test, Shenwo power plant
CLC Number:
TV734.4
TIAN Bo, YANG Fa-hong. Application of Constant α Control Method of Excitation Regulator in Shenwo Power Plant[J]. Journal of Changjiang River Scientific Research Institute, 2016, 33(2): 128-130.
0 / / Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: http://ckyyb.crsri.cn/EN/10.11988/ckyyb.20140834
http://ckyyb.crsri.cn/EN/Y2016/V33/I2/128